Goodrive300-01A series VFD for air compressor
Function description
-93-
Function
code
Name
Description
Default
Modify
P21.14
Display
current of B
phase of the
fan
0.0
–40.0A
0.0A
●
P21.15
Display
current of C
phase of the
fan
0.0
–40.0A
0.0A
●
P21.16
Sampling
value of A
phase current
zero drift
0
–4095
0
●
P21.17
Sampling
value of B
phase current
zero drift
0
–4095
0
●
P21.18
Sampling
value of C
phase current
zero drift
0
–4095
0
●
P21.20
Fan state
0X0000
–0XFFFF
Bit0: When it is 1, it indicates that
power-frequency fan is started
0x0000
●
P25 group Fault policy
Function
code
Name
Description
Default
Modify
P25.00
User-defined
fault action
selection 1
0
–0x6666
Ones: Inverter unit U phase protection (OUt1)
Tens: Inverter unit V phase protection (OUt2)
Hundreds: Inverter unit W phase protection
(OUt3)
Thousands:
Overcurrent at acceleration
(OC1)
For details about P25 group fault policy
function, see section 5.3
“Fault policy function
d
escription”.
0x0000
○