Goodrive300-01A series VFD for air compressor
External optional accessories
-147-
03.17 16:02:35
Home
Max Ouput Freq xxx.xx Hz
Return
Edit
Master Param
Run Freq Up limit xxx.xx Hz
Run Freq Down limit xxx.xx Hz
Load Run Low Limit Freq xxx.xx Hz
No-load Run Freq xxx.xx Hz
Acc time xxxx.x s
03.17 16:02:35
Home
PID Output Downlimit xxxx.x %
Return
Edit
Master param
Prop Gain xxx.xx
Integral Time xxx.xx s
Differential Time xxx.xx s
PID Output Uplimit xxxx.x %
Sample Cycle xx.xxx s
Figure B-35 Master parameter interface
Master parameter
Initial value
Function
Proportional gain
(Kp)
10.00
It indicates the speed of tracking the set working
pressure. A greater value indicates a higher speed
of tracking and easier oscillation. A smaller value
indicates a lower speed of tracking and slower
adjustment. The recommended setting range is
5.00
–15.00.
Integral time
2.00
The recommended setting range is 2.00
–4.00.
Differential time (Td)
1.00
It is used for lag tracking on the large-scale lag
system (such as temperature).
Sampling time (T)
0.100s
It indicates the sampling period for feedback values.
PID output upper
limit
100%
It indicates the upper limit of the output of the PID
regulator.
PID output lower
limit
0.0%
It indicates the lower limit of the output of the PID
regulator. It is set based on the lower limit
frequency.
Max. output
frequency
50.00Hz
It indicates the maximum output frequency of the
VFD.