Goodrive300-01A series VFD for air compressor
Function description
-99-
Fault policy
function selection
Meaning
for more than 10 minutes, the VFD will automatically clear the
cumulative number of automatic resets times (P17.18).
If you press the RST key during auto fault reset, auto fault reset is
stopped forcibly, and the number of automatic fault reset times
(P17.18) is cleared.
3
Same functions as above 2.
The difference is that the function codes for the number of auto fault
reset times and the auto fault reset interval are different. P25.13
and P25.14 are for policy 3 while P08.28 and P08.29 are for policy
2.
It allows the user to select different automatic fault reset times and
intervals for different faults in some special situations.
4
Do not deal with the fault during operation when a fault occurs.
Troubleshooting only during downtime
If a fault occurs during operation, the fault is not be reported and
the VFD still operates normally, but the warning code (P17.39) is
displayed and the keypad TRIP light flashes.
5
After a fault occurs, no fault is reported, and only a warning is given.
When the VFD is in the stopping or running state, if a fault occurs,
no fault is reported, only a warning code (P17.39) is displayed, and
the keypad TRIP indicator flashes.
6
Directly shield the fault when a fault occurs.
When a fault occurs, neither a fault nor a warning code is reported,
and the keypad TRIP indicator does not flash.
Table 5-2 Factory default fault policies
Item
Fault
Factory default fault policy functions
0
1
2
3
4
5
6
0
No fault
/
/
/
/
/
/
1
Inverter unit U phase
protection (OUt1)
✔
2
Inverter unit V phase
protection (OUt2)
✔
3
Inverter unit W phase
protection (OUt3)
✔
4
Overcurrent at acceleration
(OC1)
✔