Goodrive300-01A series VFD for air compressor
Function description
-62-
Function
code
Name
Description
Default
Modify
P08.16
Low-voltage
protection
threshold
0.0V
–2000.0V
300.0V
○
P08.17
Overvoltage
pre-protection
threshold
0.0V
–2000.0V
780.0V
○
P08.18
Automatic
restart delay
0.0
–6000.0s
60.0s
○
P08.19
Low-voltage
frequency limit
running time
0.0
–6000.0s
60.0s
○
P08.20
High-frequency
current loop
proportional
gain
0
–20000
1000
○
P08.21
High-frequency
current loop
integral time
0
–20000
1000
○
P08.23
High-frequency
current loop
switching
frequency
0.0
–100.0% (max. output frequency
100.0%
○
P08.25
Keypad lock
enable
0: Do not lock keypad
1: Allow to lock keypad
Lock: Press PRG key+DATA key
simultaneously
Unlock: Keep DATA key pressed down and
then click V key by three times.
0
○
P08.26
Maintenance
timing mode
0: No timing during sleep
1: Timing during sleep
0
○
P08.27
SM
optimization
mode selection
0: Enable
Applicable to surface-mounted synchronous
motors. The actual values of P02.21
1
○