Goodrive300-01A series VFD for air compressor
Function description
-94-
Function
code
Name
Description
Default
Modify
P25.01
User-defined
fault action
selection 2
0
–0x6666
Ones: Overcurrent at deceleration (OC2)
Tens: Overcurrent at constant speed (OC3)
Hundreds: Overvoltage at acceleration (OV1)
Thousands: Overvoltage at deceleration
(OV2)
0x0000
○
P25.02
User-defined
fault action
selection 3
0
–0x6666
Ones: Overvoltage at constant speed (OV3)
Tens: Bus undervoltage fault (UV)
Hundreds: Motor overload (OL1)
Thousands: VFD overload (OL2)
0x0020
○
P25.03
User-defined
fault action
selection 4
0
–0x6666
Ones: Phase loss on input side (SPI)
Tens: Phase loss on output side (SPO)
Hundreds: Reserved
Thousands: Inverter module overheating
(OH2)
0x0002
○
P25.04
User-defined
fault action
selection 5
0
–0x6666
Ones: External fault (EF)
Tens: RS485 communication fault (CE)
Hundreds: Current detection fault (ItE)
Thousands: Motor autotuning fault (tE)
0x0020
○
P25.05
User-defined
fault action
selection 6
0
–0x6666
Ones: EEPROM operation fault (EEP)
Tens: PID feedback sensor offline (PIDE)
Hundreds: Reserved
Thousands: Running time reached (END)
0x0020
○
P25.06
User-defined
fault action
selection 7
0
–0x6666
Ones: Electronic overload (OL3)
Tens: Reserved
Hundreds: Reserved
Thousands place: Reserved
0x0002
○
P25.07
User-defined
fault action
selection 8
0
–0x6666
Ones: Reserved
Tens: Input overvoltage (IOV)
Hundreds: Input undervoltage (IUV)
Thousands: To-ground short circuit fault 1
(ETH1)
0x0220
○