Goodrive300-01A series VFD for air compressor
Function description
-71-
Function
code
Name
Description
Default
Modify
P11.10
Overload
pre-alarm
detection time
0.1
–3600.00s
1.0s
○
P11.11
Underload
pre-alarm
detection level
0%
50%
○
P11.12
Underload
pre-alarm
detection time
0.1
–3600.0s
1.0s
○
P11.13
Fault output
terminal action
during fault
0x00
–0x11
LED ones:
0: Act during undervoltage fault
1: Do not act during undervoltage fault
LED tens:
0: Act during automatic reset period
1: Do not act during automatic reset period
0x00
○
P11.14
Speed deviation
detection value
0.0
–50.0%
10.0%
○
P11.15
Speed deviation
detection time
0.0
–10.0s (Speed deviation protection is
disabled when P11.15 is set to 0.0.)
0.5s
○
P11.16
Automatic
frequency
reduction during
voltage drop
0: Invalid
1: Valid
1
○
P13 group Synchronous motor control parameters
Function
code
Name
Description
Default
Modify
P13.00
Pull-in current
reduction
coefficient
0.0
–100.0%
50.0%
○
P13.01
Initial magnetic
pole detection
mode
0: Do not detect
1: High-frequency superposition (reserved)
2: Pulse superposition (reserved)
0
◎
P13.02
Pull-in current 1
0.0%
–100.0% (of the rated current of the
motor)
20.0%
○
P13.03
Pull-in current 2
0.0%
–100.0% (of the rated current of the
motor)
10.0%
○