Device-specific CR2052
Receive PDO communication parameters (index 0x1400…0x14FF):
Index
S-idx Designation
Data type
Default
Details
0x1400 0x00 Receive PDO
Communica-
tion Parame-
ter Number of
entries
ro
USINT
0x02
Receive PDO 1: binary outputs 0 - 7
number of entries = 2
0x01 COBID used
by PDO
rw
UDINT
0x200 + node
ID
CAN ID of the first read PDO
Bit 31 = 0 → PDO is valid
Bit 31 = 1 → PDO is not valid
0x02 transmission
type
rw
USINT
0x01
0x00 = synch acyclic
0x01���0xF0 = synch cyclic; outputs
are only updated after „n" synch
objects
n = 1…240 = 0x01���0xF0
0xFC/0xFD not implemented
0xFE = asynch man� spec� event;
outputs are updated immediately
0xFF = asynch device profile event;
outputs are updated immediately
0x1401 0x00 Receive PDO
Communica-
tion Parame-
ter Number of
entries
ro
USINT
0x02
Receive PDO 2: PWM outputs 0 - 3
number of entries = 2
0x01 COBID used
by PDO
rw
UDINT
0x300 + node
ID
CAN ID of the second read PDO
Bit 31 = 0 → PDO is valid
Bit 31 = 1 → PDO is not valid
0x02 transmission
type
rw
USINT
0x01
0x00 = synch acyclic
0x01���0xF0 = synch cyclic; outputs
are only updated after „n" synch
objects
n = 1…240 = 0x01���0xF0
0xFC/0xFD not implemented
0xFE = asynch man� spec� event;
outputs are updated immediately
0xFF = asynch device profile event;
outputs are updated immediately