UK
ioControl
71
Index
S-idx Designation
Data type
Default
Details
0x1604 0x00 Receive PDO
mapping
Number of
mapped
objects in
PDO
rw
USINT
0x04
Mapping read PDO 5:
PWM outputs OUT12…OUT15
number of integrated application
objects = 4
0x01 PDO map-
ping
rw
UDINT
0x6414 0D10 PWM/ current output OUT12
Index 0x6414, SubIndex 0x0D
contains the preset value of the
PWM output OUT12, the value is
interpreted as duty cycle in ‰ or as
target current value (depending on
the configuration index 0x2000)
0x02 PDO map-
ping
rw
UDINT
0x6414 0E10 PWM/ current output OUT13
Index 0x6414, SubIndex 0x0E
contains the preset value of the
PWM output OUT13, the value is
interpreted as duty cycle in ‰ or as
target current value (depending on
the configuration index 0x2000)
0x03 PDO map-
ping
rw
UDINT
0x6414 0F10 PWM/ current output OUT14
Index 0x6414, SubIndex 0x0F
contains the preset value of the
PWM output OUT14, the value is
interpreted as duty cycle in ‰ or as
target current value (depending on
the configuration index 0x2000)
0x04 PDO map-
ping
rw
UDINT
0x6414 1010
PWM/ current output OUT15
Index 0x6414, SubIndex 0x10
contains the preset value of the
PWM output OUT15, the value is
interpreted as duty cycle in ‰ or as
target current value (depending on
the configuration index 0x2000)