ioControl
104
Transmit PDO mapping (index 0x1A00…0x1AFF):
Index
S-idx Designation
Data type
Default
Details
0x1A00 0x00 Transmit
PDO map-
ping
Number of
mapped
objects in
PDO
rw
USINT
0x07
mapping transmit PDO 1
number of integrated application
objects = 7
0x01 PDO map-
ping
rw
UDINT
0x6000 0108
Index 0x6000, SubIndex 0x01
binary inputs 00���07: actual values
(bit coded)
0x02 PDO map-
ping
rw
UDINT
0x2020 0108
Index 0x2020, SubIndex 0x01
binary inputs 00���07: flag "short
circuit" (bit coded)
0x03 PDO map-
ping
rw
UDINT
0x2021 0108
Index 0x2021, SubIndex 0x01
binary inputs 00���07: flag "wire break"
(bit coded)
0x04 PDO map-
ping
rw
UDINT
0x2025 0108
Index 0x2025, SubIndex 0x01
inputs 00, 01, 04 und 05: flag "over-
load" (bit coded)
0x05 PDO map-
ping
rw
UDINT
0x2022 0108
Index 0x2022, SubIndex 0x01
outputs 00���07: flag " short circuit "
(bit coded)
0x06 PDO map-
ping
rw
UDINT
0x2023 0108
Index 0x2023, SubIndex 0x01
outputs 00���07: flag " wire break " (bit
coded)
0x07 PDO map-
ping
rw
UDINT
0x2024 0108
Index 0x2024, SubIndex 0x01
outputs 00���07: flag " overload " (bit
coded)