ioControl
126
Index
S-idx Designation
Data type
Default Details
0x2022 0x00 Output – short
circuit
ro
USINT
1
Largest sub-index supported
0x01 Short circuit
OUT00…OUT07
ro
USINT
0
0 = normal
1 = short circuit
channels (bit coded)
0b---- ---X = OUT00
0b---- --X- = OUT01
0b---- -X-- = OUT02
0b---- X--- = OUT03
0b---X ---- = OUT04
0b--X- ---- = OUT05
0b-X-- ---- = OUT06
0bX--- ---- = OUT07
0x2023 0x00 Output – open
circuit
ro
USINT
1
Largest sub-index supported
0x01 Open circuit
OUT00…OUT07
ro
USINT
0
0 = normal
1 = open circuit
channels (bit coded)
0b---- ---X = OUT00
0b---- --X- = OUT01
0b---- -X-- = OUT02
0b---- X--- = OUT03
0b---X ---- = OUT04
0b--X- ---- = OUT05
0b-X-- ---- = OUT06
0bX--- ---- = OUT07
0x2024 0x00 Output – overload ro
USINT
1
Largest sub-index supported
0x01 Overload
OUT00…OUT07
ro
USINT
0
0 = normal
1 = overload
channels (bit coded)
0b---- ---X = OUT00
0b---- --X- = OUT01
0b---- -X-- = OUT02
0b---- X--- = OUT03
0b---X ---- = OUT04
0b--X- ---- = OUT05
0b-X-- ---- = OUT06
0bX--- ---- = OUT07
0x2025 0x00 Input analog –
overcurrent
ro
USINT
1
Largest sub-index supported
0x01 Overcurrent IN00,
IN01, IN04 und
IN05
ro
USINT
0
0 = normal
1 = overcurrent
channels (bit coded)
0b---- ---X = IN00
0b---- --X- = IN01
0b---- -X-- = IN04
0b---- X--- = IN05