ioControl
60
Index
S-idx Designation
Data type
Default
Details
0x2000 0x0A Configuration
IN09
rw
USINT
01
0 = 0x00
01 = 0x01
14 = 0x0E
20 = 0x14
off Input IN09
binary plus switched
frequency 0…30
000 Hz
period duration
0x0B Configuration
IN10
rw
USINT
10
0 = 0x00
10 = 0x0A
11 = 0x0B
18 = 0x12
off Input IN10
binary plus switched
binary plus switched
with diagnosis
16…30 000 Ohm
0x0C Configuration
IN11
rw
USINT
01
0 = 0x00
01 = 0x01
14 = 0x0E
20 = 0x14
off Input IN11
binary plus switched
frequency 0…30
000 Hz
period duration
0x0D Configuration
IN12
rw
USINT
10
0 = 0x00
10 = 0x0A
11 = 0x0B
18 = 0x12
off Input IN12
binary plus switched
binary plus switched
with diagnosis
16…30 000 Ohm
0x0E Configuration
IN13
rw
USINT
01
0 = 0x00
01 = 0x01
14 = 0x0E
20 = 0x14
off Input IN12
binary plus switched
frequency 0…30
000 Hz
period duration
0x0F Configuration
IN14
rw
USINT
10
0 = 0x00
10 = 0x0A
11 = 0x0B
18 = 0x12
off Input IN14
binary plus switched
binary plus switched
with diagnosis
16…30 000 Ohm
0x10 Configuration
IN15
rw
USINT
01
0 = 0x00
01 = 0x01
14 = 0x0E
20 = 0x14
off Input IN15
binary plus switched
frequency 0…30
000 Hz
period duration
0x2012 0x00 Period input
ro
USINT
4
Largest sub-index supported
0x01 Period durati-
on IN09
ro
UDINT
0
IN09 period duration [µs]
0x02 Period durati-
on IN11
ro
UDINT
0
IN11 period duration [µs]
0x03 Period durati-
on IN13
ro
UDINT
0
IN13 period duration [µs]
0x04 Period durati-
on IN15
ro
UDINT
0
IN15 period duration [µs]