UK
ioControl
59
Index
S-idx Designation
Data type
Default
Details
0x2000 0x04 Configuration
IN03
rw
USINT
10
0 = 0x00
3 = 0x03
6 = 0x06
7 = 0x07
9 = 0x09
10 = 0x0A
11 = 0x0B
12 = 0x0C
off Input IN03
0���10 000 mV
ratiometric 0���1000 ‰
0���20 000 µA
0���32 000 mV
binary plus switched
binary plus switched
with diagnosis
binary minus switched
0x05 Configuration
IN04
rw
USINT
10
0 = 0x00
3 = 0x03
6 = 0x06
7 = 0x07
9 = 0x09
10 = 0x0A
11 = 0x0B
12 = 0x0C
off Input IN04
0���10 000 mV
ratiometric 0���1000 ‰
0���20 000 µA
0���32 000 mV
binary plus switched
binary plus switched
with diagnosis
binary minus switched
0x06 Configuration
IN05
rw
USINT
10
0 = 0x00
3 = 0x03
6 = 0x06
7 = 0x07
9 = 0x09
10 = 0x0A
11 = 0x0B
12 = 0x0C
off Input IN05
0���10 000 mV
ratiometric 0���1000 ‰
0���20 000 µA
0���32 000 mV
binary plus switched
binary plus switched
with diagnosis
binary minus switched
0x07 Configuration
IN06
rw
USINT
10
0 = 0x00
3 = 0x03
6 = 0x06
7 = 0x07
9 = 0x09
10 = 0x0A
11 = 0x0B
12 = 0x0C
off Input IN06
0���10 000 mV
ratiometric 0���1000 ‰
0���20 000 µA
0���32 000 mV
binary plus switched
binary plus switched
with diagnosis
binary minus switched
0x08 Configuration
IN07
rw
USINT
10
0 = 0x00
3 = 0x03
6 = 0x06
7 = 0x07
9 = 0x09
10 = 0x0A
11 = 0x0B
12 = 0x0C
off Input IN07
0���10 000 mV
ratiometric 0���1000 ‰
0���20 000 µA
0���32 000 mV
binary plus switched
binary plus switched
with diagnosis
binary minus switched
0x09 Configuration
IN08
rw
USINT
10
0 = 0x00
10 = 0x0A
11 = 0x0B
18 = 0x12
off Input IN08
binary plus switched
binary plus switched
with diagnosis
16…30 000 Ohm