TXD1 (Transmit 1)
Applicable CPU Modules
TXD2 (Transmit 2)
Applicable CPU Modules
Valid Operands
For the valid operand number range, see pages 6-1 and 6-2.
▲
Internal relays M0 through M1277 can be designated as D1. Special internal relays cannot be designated as D1.
Transmit data designated by operand S1 can be a maximum of 200 bytes.
When transmission is complete, an output or internal relay, designated by operand D1, is turned on.
Destination 2 occupies two consecutive data registers starting with the operand designated by D2. The transmit status data
register, D0 through D1298 or D2000 through D7998, stores the status of transmission and error code. The next data regis-
ter stores the byte count of transmitted data. The same data registers can not be used as transmit status registers for TXD1/
TXD2 instructions and receive status registers for RXD1/RXD2 instructions.
The TXD1/TXD2 instructions cannot be used in an interrupt program. If used, a user program execution error will result,
turning on special internal relay M8004 and the ERR LED on the CPU module.
Precautions for Programming TXD Instruction
•
The MicroSmar t has five formatting areas each for executing TXD1 and TXD2 instructions, so five TXD1 and five TXD2
instructions can be processed at the same time. If inputs to more than five TXD1 or TXD2 instructions are turned on at the
same time, an error code is set to the transmit status data register, designated by operand D2, in the excessive TXD
instructions that cannot be executed.
•
If the input for a TXD instruction is turned on while another TXD instruction is executed, the subsequent TXD instruction is
executed 2 scan times after the preceding TXD instruction is completed.
•
Since TXD instructions are executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction should
be used as required.
FC4A-C10R2/C
FC4A-C16R2/C
FC4A-C24R2/C
FC4A-D20K3/S3
FC4A-D20RK1/RS1 & FC4A-D40K3/S3
X
X
X
X
X
FC4A-C10R2/C
FC4A-C16R2/C
FC4A-C24R2/C
FC4A-D20K3/S3
FC4A-D20RK1/RS1 & FC4A-D40K3/S3
—
X
X
X
X
Operand
Function
I
Q
M
R
T
C
D
Constant
Repeat
S1 (Source 1)
Transmit data
—
—
—
—
—
—
X
X
—
D1 (Destination 1)
Transmit completion output
—
X
▲
—
—
—
—
—
—
D2 (Destination 2)
Transmit status register
—
—
—
—
—
—
X
—
—
When input is on, data designated by S1 is conver ted into a specified
format and transmitted through por t 1 to a remote terminal with an
RS232C por t.
TXD
1
S1
*****
D1
*****
D2
*****
When input is on, data designated by S1 is conver ted into a specified
format and transmitted through por t 2 to a remote terminal with an
RS232C. Upgraded CPU modules can also use the RS485 por t.
TXD
2
S1
*****
D1
*****
D2
*****
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...