2: M
ODULE
S
PECIFICATIONS
2-46
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
Analog Input Specifications (END Refresh Type)
For Note 1 through Note 3, see page 2-50.
Type No.
FC4A-L03A1 / FC4A-J2A1
FC4A-L03AP1
Analog Input Signal Type
Voltage Input
Current Input
Thermocouple
Resistance
Thermometer
Input Range
0 to 10V DC
4 to 20 mA DC
Type K
(0 to 1300°C)
Type J
(0 to 1200°C)
Type T
(0 to 400°C)
Pt 100
3-wire type
(–100 to 500°C)
Input Impedance
1 M
Ω
minimum
10
Ω
1 M
Ω
minimum
1 M
Ω
minimum
Allowable Conductor Resistance
(per wire)
—
—
—
200
Ω
maximum
Input Detection Current
—
—
—
1.0 mA maximum
AD
Conversion
Sample Duration Time
20 ms maximum
20 ms maximum
Sample Repetition Time
20 ms maximum
20 ms maximum
Total Input System
Transfer Time
(Note 1)
105 ms + 1 scan time
200 ms + 1 scan time
Type of Input
Single-ended
input
Differential input
Operating Mode
Self-scan
Conversion Method
∑∆
type ADC
Input Error
Maximum Error at 25°C
±0.2% of full scale
±0.2% of full scale
+ cold junction
compensation
error
(±4°C maximum)
±0.2% of full
scale
Temperature Coefficient
±0.006% of full scale/°C
Repeatability after
Stabilization Time
±0.5% of full scale
Non-lineality
±0.2% of full scale
Maximum Error
±1% of full scale
Data
Digital Resolution
4096 increments (12 bits)
Input Value of LSB
2.5 mV
4 µA
K: 0.325°C
J: 0.300°C
T: 0.100°C
0.15°C
Data Type in Application
Program
Default:
0 to 4095
Optional: –32768 to 32767 (selectable for each channel) (Note 2)
Monotonicity
Yes
Input Data Out of Range
Detectable (Note 3)
Noise
Resistance
Maximum Temporary
Deviation during Electrical
Noise Tests
±3% maximum
(when a 500V clamp voltage is applied to the power
supply and I/O lines)
Not assured
Input Filter
No
Recommended Cable for
Noise Immunity
Twisted pair shielded cable
—
Crosstalk
2 LSB maximum
Isolation
Between input and power circuit:
Isolated
Between input and internal circuit:
Photocoupler-isolated
Effect of Improper Input Connection
No damage
Maximum Permanent Allowed Overload
(No Damage)
13V DC
40 mA DC
—
Selection of Analog Input Signal Type
Using programming software
Calibration or Verification to Maintain
Rated Accuracy
Not possible
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...