24: A
NALOG
I/O C
ONTROL
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
24-11
Analog Input Parameters
Analog input parameters include the analog input signal type, analog input data type, analog input minimum and maxi-
mum values, filter value, thermistor parameter, analog input data, and analog input operating status. This section describes
these parameters in detail.
Analog Input Signal Type
A total of 11 analog input signal types are available, depending on the analog I/O or analog input module. Select an analog
input signal type for each analog input channel. When a channel is not used, select the default value or
Not used
for the
channel.
Analog Input Data Type
A total of five analog input data types are available, depending on the analog I/O or analog input module. Select an analog
input data type for each analog input channel.
Binary Data
When Binary data is selected as an analog input data type, the analog input is linearly converted into digital data in the
range described in the table below.
Parameter
FC4A-
L03A1
FC4A-
L03AP1
FC4A-
J2A1
FC4A-
J4CN1
FC4A-
J8C1
FC4A-
J8AT1
0
Voltage input (0 to 10V DC)
X
—
X
X
X
—
1
Current input (4 to 20 mA DC)
X
—
X
X
X
—
2
Type K thermocouple
—
X
—
X
—
—
3
Type J thermocouple
—
X
—
X
—
—
4
Type T thermocouple
—
X
—
X
—
—
5
Pt 100 resistance thermometer
—
X
—
X
—
—
6
Pt 1000 resistance thermometer
—
—
—
X
—
—
7
Ni 100 resistance thermometer
—
—
—
X
—
—
8
Ni 1000 resistance thermometer
—
—
—
X
—
—
9
NTC type thermistor
—
—
—
—
—
X
10
PTC type thermistor
—
—
—
—
—
X
255
Not used
—
—
—
X
X
X
Parameter
FC4A-
L03A1
FC4A-
L03AP1
FC4A-
J2A1
FC4A-
J4CN1
FC4A-
J8C1
FC4A-
J8AT1
0
Binar y data
X
X
X
X
X
X
1
Optional range
X
X
X
X
X
X
2
Celsius
—
X
—
X
—
NTC only
3
Fahrenheit
—
X
—
X
—
NTC only
4
Resistance
—
—
—
—
—
X
Type No.
FC4A-L03A1
FC4A-L03AP1
FC4A-J2A1
FC4A-J4CN1
FC4A-J8C1
FC4A-J8AT1
Analog Input Data
0 to 4095
Analog Input Signal Type Analog Input Data
Voltage/Current:
0 to 50,000
Thermocouple:
0 to 50,000
Pt100, Ni100:
0 to 6,000
Pt1000, Ni1000:
0 to 60,000
0 to 50000
0 to 4000
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...