Interrupt Input
All
MicroSmart
CPU modules have an interrupt input function. When a quick response to an external input is required,
such as positioning control, the interrupt input can call a subroutine to execute an interrupt program.
Four inputs I2 through I5 can be designated to execute interrupt at a rising and/or falling edge of input pulses. When an
interrupt is initiated by inputs I2 through I5, program execution immediately jumps to a predetermined label number
stored in special data registers D8032 through D8035, respectively. The Function Area Settings dialog box is used to des-
ignate inputs I2 through I5 as an interrupt input, normal input, high-speed counter input, or catch input.
Normal input signals to input terminals are read when the END instruction is executed at the end of a scan.
Since these settings relate to the user program, the user program must be downloaded to the
MicroSmart
after changing
any of these settings.
Interrupt Input Terminals, Special Data Registers, and Special Internal Relays for Interrupt Inputs
Programming WindLDR
1.
From the
WindLDR
menu bar, select
Configure
>
Function Area Settings
. The Function Area Settings dialog box
appears.
2.
Select the
Special Input
tab.
3.
Select
Interrupt Input
in the Groups 1 through 4 pull-down list boxes. the Interrupt Input dialog box appears.
4.
Select an interrupt edge in the pull-down list for each group.
Disable and Enable Interrupts
The interrupt inputs I2 through I5 and timer interrupt are normally enabled while the CPU is running, and can also be indi-
vidually disabled using the DI instruction or enabled using the EI instruction. When interrupt inputs I2 through I5 are
enabled, special internal relay M8140 through M8143 are turned on, respectively. See page 18-7.
Group
Interrupt Input No.
Interrupt Input Jump Destination Label No.
Interrupt Input Status
Group 1
I2
D8032
M8140
Group 2
I3
D8033
M8141
Group 3
I4
D8034
M8142
Group 4
I5
D8035
M8143
Interrupt Input Rising/Falling Edge Selection
Interrupt at Rising Edge
Interrupt occurs when the interrupt input
turns on.
Interrupt at Falling Edge
Interrupt occurs when the interrupt input
turns off.
Interrupt at Both Edges
Interrupt occurs when the interrupt input
turns on or off.
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...