7: B
ASIC
I
NSTRUCTIONS
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
7-9
Timer Accuracy, continued
Timer Counting Error
Every timer instruction operation is individually based on asynchronous 16-bit reference timers. Therefore, an error occurs
depending on the status of the asynchronous 16-bit timer when the timer instruction is executed.
Timeout Output Error
The output RAM status is set to the actual output when the END instruction is processed. So, an error occurs depending on
the timing when the timeout output turns on in a scan cycle. The timeout output error shown below does not include output
delay caused by the hardware.
Maximum and Minimum of Errors
Notes:
Advance error does not occur at the timer input and timeout output.
Tet + Tte = 1 scan time
Increment is 1 sec (TML), 100 ms (TIM), 10 ms (TMH), or 1 ms (TMS).
The maximum advance error is: Increment – 1 scan time
The maximum behind error is: 3 scan times
The timer input error and timeout output error shown above do not include the input response time (behind error)
and output response time (behind error) caused by hardware.
Power Failure Memory Protection
Timers TML, TIM, TMH, and TMS do not have power failure protection. A timer with this protection can be devised using
a counter instruction and special internal relay M8121 (1-sec clock), M8122 (100-ms clock), or M8123 (10-ms clock).
Error
TML
(1-sec timer)
TIM
(100-ms timer)
TMH
(10-ms timer)
TMS
(1-ms timer)
Maximum
Advance error
1000 ms
100 ms
10 ms
1 ms
Behind error
1 scan time
1 scan time
1 scan time
1 scan time
Error
Timer Input Error
Timer Counting
Error
Timeout Output
Error
Total Error
Minimum
Advance error
0 (Note)
0
0 (Note)
0
Behind error
Tet
0
Tte
0
Maximum
Advance error
0 (Note)
Increment
0 (Note)
Increment – (Tet + Tte)
Behind error
1 scan time + Tet
1 scan time
Tte
2 scan times + (Tet + Tte)
Program Processing
Timeout Output RAM
ON
OFF
Actual Output
ON
OFF
END
1 scan time
TIM
END
Tte
Timeout output error is equal to Tte (behind error) and can
be between 0 and one scan time.
0 < Tte < 1 scan time
Tte: Time from the timer instruction execution to the END
processing
Ladder Diagram
I1
I1
ON
OFF
C2
ON
OFF
Timing Chart
10 sec
(10-sec Timer)
CNT
C2
1000
M8123
Reset
Pulse
Instruction
Data
LODN
LOD
CNT
I1
M8123
C2
1000
Program List
Note:
Designate counter C2 used in this program as a keep type counter. See page 5-4.
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...