3: I
NSTALLATION
AND
W
IRING
3-18
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
Terminal Connection
Ferrules, Crimping Tool, and Screwdriver for Phoenix Terminal Blocks
The screw terminal block can be wired with or without using ferrules on the end of cable. Applicable ferrules for the Phoe-
nix terminal blocks and crimping tool for the ferrules are listed below. The screwdriver is used for tightening the screw ter-
minals on the
MicroSmart
modules. These ferrules, crimping tool, and screwdriver are made by Phoenix Contact and are
available from Phoenix Contact.
Type numbers of the ferrules, crimping tool, and screwdriver listed below are the type numbers of Phoenix Contact. When
ordering these products from Phoenix Contact, specify the Order No. and quantity listed below.
Ferrule Order No.
Crimping Tool and Screwdriver Order No.
Quantity of Cables
Cable Size
Phoenix Type
Order No.
Pcs./Pkt.
For 1-cable connection
UL1007 AWG16
AI 1,5-8 BK
32 00 04 3
100
UL1007 AWG18
AI 1-8 RD
32 00 03 0
100
UL1015 AWG22
AI 0,5-8 WH
32 00 01 4
100
For 2-cable connection
UL1007 AWG18
AI-TWIN 2 x
0,75-8 GY
32 00 80 7
100
UL1015 AWG22
AI-TWIN 2 x 0,5-8 WH
32 00 93 3
100
Tool Name
Phoenix Type
Order No.
Pcs./Pkt.
Crimping Tool
CRIMPFOX ZA 3
12 01 88 2
1
Screwdriver
For CPU modules
SZS 0,6 x 3,5
12 05 05 3
10
For I/O modules and
communication adapter
SZS 0,4 x 2,5
12 05 03 7
10
Screw Terminal Tightening Torque
CPU modules
0.5 N·m
I/O modules
Communication adapter
0.22 to 0.25 N·m
Caution
•
Make sure that the operating conditions and environments are within the specification values.
•
Be sure to connect the grounding wire to a proper ground, otherwise electrical shocks may be
caused.
•
Do not touch live terminals, otherwise electrical shocks may be caused.
•
Do not touch terminals immediately after power is turned off, otherwise electrical shocks may be
caused.
•
When using ferrules, insert a wire to the bottom of the ferrule and crimp the ferrule.
•
When connecting a stranded wire or multiple solid wires to a screw terminal block, use a ferrule.
Otherwise the wire may slip off the screw terminal block.
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...