27: M
ODEM
M
ODE
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
27-7
Modem Mode Status Data Register
When the modem mode is enabled, data register D8111 stores a modem mode status or error code.
D8111 Value
Status
Description
0
Not in the modem mode
Modem mode is not enabled.
10
Ready for connecting line
Star t internal relays except for disconnecting line can
be turned on.
20
Sending initialization string
(originate mode)
A star t internal relay is in operation in the first tr y or
subsequent retrial.
21
Sending ATZ (originate mode)
22
Dialing
23
Disconnecting line
24
Sending AT command
25
Sending initialization string (answer mode)
26
Sending ATZ (answer mode)
30
Waiting for resending initialization string
(originate mode)
The command star ted by a star t internal relay was not
completed and is waiting for retrial.
31
Waiting for resending ATZ (originate mode)
32
Waiting for re-dialing
33
Waiting for re-disconnecting line
34
Waiting for resending AT command
35
Waiting for resending initialization string
(answer mode)
36
Waiting for resending ATZ (answer mode)
40
Line connected
Telephone line is connected. Only M8053 (disconnect
line) can be turned on.
50
AT command completed successfully
Command star ted by M8054-M8056 is completed suc-
cessfully.
60
AT command program error
Invalid character is included in the initialization string,
dial number, or AT command string.
Correct the program to include 0Dh in the AT command.
61
Simultaneous star t of commands
Two or more star t internal relays are on.
Correct the user program so that only one star t internal
relay goes on at a time.
62
Invalid command in on-line mode
A star t IR other than M8053 (disconnect line) is turned
on while the telephone line is connected.
Correct the program so that only the disconnect com-
mand is sent while the line is connected.
63
AT command execution error
Command failed in the first and all retr y cycles.
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...