28: AS-I
NTERFACE
M
ASTER
C
OMMUNICATION
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
28-7
Power Supply
Power Supply Wiring Diagram
A recommended power supply wiring diagram is shown below. Use a common power switch for both the CPU module
power supply and AS-Interface power supply to make sure that both power supplies are turned on and off at the same time.
Note:
A failed slave can be replaced with a new slave with address 0 without turning off the power to the CPU module and
the AS-Inter face line. But, if power has been turned off before replacing the slaves, install a new slave with address 0 and
take one of the following steps, because the AS-Inter face master module has to be initialized to enable communication.
•
Disconnect the AS-Inter face cable connector and turn on both power supplies. Five seconds later, connect the AS-Inter face
cable connector.
•
Turn on the CPU module power supply first. Five seconds later, turn on the AS-Inter face power supply.
•
When turning off the power to the CPU module, also turn off the AS-Interface power supply. If the
CPU module is powered down and up while the AS-Interface power remains on, AS-Interface com-
munication may stop due to a configuration error, resulting in a communication error.
•
Turn on the AS-Interface power supply no later than the CPU module power supply, except when
slave address 0 exists on the network. The two power supplies may be turned off in any order.
•
Immediately after power-up, the CPU module cannot access slave I/O data in the AS-Interface mas-
ter module. Make the user program so that slave I/O data are accessed after special internal relay
M1945 (Normal_Operation_Active) has turned on. See page 28-24.
Caution
AS-Interface Power Supply
30V DC
Slim Type CPU Module
FC4A-D40K3
AS-Inter face Master Module
FC4A-AS62M
Slave 1
Slave 2
AC Power
CPU Module Power Supply
24V DC
Power Switch
AS-Inter face Power Switch (Note)
AS-Inter face Cable Connector
VLSV (ver y low safety voltage)
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...