13-5
WSFT (Word Shift)
Applicable CPU Modules
Valid Operands
For the valid operand number range, see pages 6-1 and 6-2.
When T (timer) or C (counter) is used as S1 or S2, the timer/counter current value is read out.
Valid Data Types
Special Internal Relay M8024: BMOV/WSFT Executing Flag
While the BMOV or WSFT is executed, M8024 turns on. When completed, M8024 turns off. If the CPU is powered down
while executing BMOV or WSFT, M8024 remains on when the CPU is powered up again.
Example: WSFT
FC4A-C10R2/C
FC4A-C16R2/C
FC4A-C24R2/C
FC4A-D20K3/S3
FC4A-D20RK1/RS1 & FC4A-D40K3/S3
—
—
—
—
X
Operand
Function
I
Q
M
R
T
C
D
Constant
Repeat
S1 (Source 1)
Source data for word shift
X
X
X
X
X
X
X
X
—
S2 (Source 2)
Quantity of blocks to shift
X
X
X
X
X
X
X
X
—
D1 (Destination 1)
First operand number to shift
—
—
—
—
—
—
X
—
—
W (word)
I (integer)
X
—
When input is on, N blocks of 16-bit word data star ting with operand
designated by D1 are shifted up to the next 16-bit positions. At the
same time, the data designated by operand S1 is moved to operand
designated by D1. S2 specifies the quantity of blocks to move.
WSFT
S1
*****
D1
*****
S2
*****
When S2 = 3 (
quantity of blocks to shift)
First 16-bit data
D1+0
Second 16-bit data
D1+1
Third 16-bit data
D1+2
Fifth 16-bit data
D1+4
Four th 16-bit data
D1+3
S1 data
D1+0
First 16-bit data
D1+1
Second 16-bit data
D1+2
Fifth 16-bit data
D1+4
Third 16-bit data
D1+3
3 blocks (S2)
16-bit data
S1
16-bit data
S1
When a bit operand such as I (input), Q (output), M (internal relay), or R (shift register) is
designated as source S1 or S2, 16 points are used.
When a word operand such as T (timer), C (counter), or D (data register) is designated as
source S1 or S2, 1 point is used.
D100 through D102
→
D101 through D103
D10
→
D100
When input I0 is turned on, data of 3 data registers star ting with
D100 designated by destination operand D1 is shifted to the next
data registers. Data of data register D10 designated by source oper-
and S1 is moved to D100 designated by destination operand D1.
SOTU
I0
S1
D10
D1
D100
WSFT
S2
3
2222
D101
1111
D100
3333
D102
4444
D103
5555
D104
1111
D101
12345
D100
2222
D102
3333
D103
5555
D104
12345
D10
12345
D10
Before shift:
After first shift:
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...