2: M
ODULE
S
PECIFICATIONS
2-4
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
Function Specifications (All-in-One Type CPU Module)
CPU Module Specifications
System Statuses at Stop, Reset, and Restart
CPU Module
FC4A-C10R2
FC4A-C10R2C
FC4A-C16R2
FC4A-C16R2C
FC4A-C24R2
FC4A-C24R2C
Program Capacity
4,800 bytes
(800 steps)
15,000 bytes
(2,500 steps)
27,000 bytes
(4,500 steps)
Expandable I/O Modules
—
—
4 modules
I/O Points
Input
6
9
14
Expansion:
64
Output
4
7
10
User Program Storage
EEPROM
RAM Backup
Backup Duration
Approx. 30 days (typical) at 25°C after backup batter y fully charged
Backup Data
Internal relay, shift register, counter, data register
Battery
Lithium secondar y batter y
Charging Time
Approx. 24 hours for charging from 0% to 90% of full charge at 25°C
Battery Life
Approx. 1000 cycles of discharging down to 10% and full charging
Replaceability
Not possible to replace batter y
Control System
Stored program system
Instruction Words
35 basic
38 advanced
35 basic
40 advanced
35 basic
48 advanced
Processing
Time
Basic instruction
1.65 ms (1000 steps) See page A-1.
END processing
0.64 ms (not including expansion I/O ser vice, clock function processing, data
link processing, and interrupt processing) See page A-2.
Internal Relay
256
1024
1024
Shift Register
64
128
128
Data Register
400
1300
1300
Counter
(adding, dual pulse reversible,
up/down selection reversible)
32
100
100
Timer
(1-sec, 100-ms, 10-ms, 1-ms)
32
100
100
Input Filter
3 to 15 ms (selectable in increments of 1 ms)
Catch Input
Interrupt Input
Four inputs (I2 through I5) can be designated as catch inputs or interrupt inputs
Minimum turn on pulse width: 40 µs maximum
Minimum turn off pulse width: 150 µs maximum
Self-diagnostic Function
Power failure, watchdog timer, data link connection, user program EEPROM sum
check, timer/counter preset value sum check, user program RAM sum check,
keep data, user program syntax, user program writing, CPU module, clock IC, I/O
bus initialize, user program execution
Start/Stop Method
Turning power on and off
Star t/stop command in WindLDR
Turning star t control special internal relay M8000 on and off
Turning designated stop or reset input off and on
Mode
Output
Internal Relay, Shift Register,
Counter, Data Register
Timer Current Value
Keep Type
Clear Type
Run
Operating
Operating
Operating
Operating
Stop (Stop input ON)
OFF
Unchanged
Unchanged
Unchanged
Reset (Reset input ON)
OFF
OFF/Reset to zero
OFF/Reset to zero
Reset to zero
Restar t
Unchanged
Unchanged
OFF/Reset to zero
Reset to preset
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...