27: M
ODEM
M
ODE
27-14
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
Troubleshooting in Modem Communication
When a start internal relay is turned on, the data of D8111 (modem mode status) changes, but the modem does
not work.
Cause:
A wrong cable is used or wiring is incorrect.
Solution:
Use the modem cable 1C (FC2A-KM1C).
The DTR or ER indicator on the modem does not turn on.
Cause:
A wrong cable is used or wiring is incorrect.
Solution:
Use the modem cable 1C (FC2A-KM1C).
When a start internal relay is turned on, the data of D8111 (modem mode status) does not change.
Cause:
Modem protocol is not selected for port 2.
Solution:
Select Modem Protocol for Port 2 using
WindLDR
(
Configure
>
Function Area Settings
>
Communica-
tion
) and download the user program to the CPU module.
When an initialization string is sent, a failure occurs, but sending ATZ completes successfully.
Cause:
The initialization string is not valid for the modem.
Solution:
Refer to the user’s manual for the modem and correct the initialization string.
When a dial command is sent, a result code “NO DIALTONE” is returned and the telephone line is not connected.
Cause 1:
The modular cable is not connected.
Solution 1:
Connect the modular cable to the modem.
Cause 2:
The modem is used in a PBX environment.
Solution 2:
Add X0 or X3 to the initialization string stored in data registers D8145-D8169, and try initialization again.
Dialing completes successfully, but the telephone line is disconnected in a short period of time.
Cause 1:
The modem settings at the both ends of the line are different.
Solution 1:
Make the same settings for the modems at the both ends.
Cause 2:
The model of the modems at the both ends of the line is different.
Solution 2
: Use the same modems at the both ends.
Cause 3:
The quality of the telephone line is low.
Solution 3:
Decrease the baud rate of the
MicroSmart
to lower than 9600 bps.
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...