S1+0 Output Pulse Frequency
The value stored in the data register designated by operand S1+0 determines the pulse output frequency.
0:
6.81 Hz (146.84 ms period)
1:
27.26 Hz (36.68 ms period)
2:
217.86 Hz (4.59 ms period)
S1+1 Pulse Width Ratio
The value stored in the data register designated by operand S1+1 specifies the pulse width ratio of the pulse output in per-
cent of the period determined by the output pulse frequency selected with S1+0. Valid values for operand S1+1 are 1
through 100.
S1+2 Pulse Counting
Pulse counting can be enabled for the PWM1 instruction only. With pulse counting enabled, PWM1 generates a predeter-
mined number of output pulses as designated by operands S1+3 and S1+4. With pulse counting disabled, PWM1 or
PWM2 generates output pulses while the start input for the PWM instruction remains on.
0:
Disable pulse counting
1:
Enable pulse counting (PWM1 only)
When programming PWM2, store 0 to the data register designated by S1+2.
S1+3 Preset Value (High Word)
S1+4 Preset Value (Low Word)
With pulse counting enabled as described above, PWM1 generates a predetermined number of output pulses as designated
by operands S1+3 and S1+4. The preset value can be 1 through 100,000,000 (05F5 E100h) stored in two consecutive data
registers designated by S1+3 (high word) and S1+4 (low word).
When pulse counting is disabled for PWM1 or when programming PWM2, store 0 to data registers designated by S1+3
and S1+4.
S1+5 Current Value (High Word)
S1+6 Current Value (Low Word)
While the PWM1 instruction is executed, the output pulse count is stored in two consecutive data registers designated by
operands S1+5 (high word) and S1+6 (low word). The current value can be 1 through 100,000,000 (05F5 E100h) and is
updated in every scan.
S1+7 Error Status
When the start input for the PWM1 or PWM2 instruction is turned on, operand values are checked. When any error is
found in the operand values, the data register designated by operand S1+7 stores an error code.
Error Code
Description
0
Normal
1
Output pulse frequency designation error (S1+0 stores other than 0 through 2)
2
Pulse width ratio designation error (S1+1 stores other than 1 through 100)
3
Pulse counting designation error (S1+2 stores other than 0 and 1)
4
Preset value designation error (S1+3 and S1+4 store other than 1 through 100,000,000)
5
Invalid pulse counting designation for PWM2 (S1+2 stores 1)
Pulse Width = Period
×
Pulse Width Ratio (%)
Pulse Width
Period
Pulse
Width
Ratio
100
----------------------------------------------
×
=
1
Output
Pulse
Frequency
--------------------------------------------------------------
Pulse
Width
Ratio
100
----------------------------------------------
×
=
Period (146.84, 36.68, or 4.59 ms)
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...