20: P
ULSE
I
NSTRUCTIONS
20-14
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
S1+0 Operation Mode
The value stored in the data register designated by operand S1+0 determines the frequency range of the pulse output.
0:
10 to 1,000 Hz
1:
100 to 10,000 Hz
2:
1,000 to 20,000 Hz
3:
10 to 20,000 Hz (upgraded CPU only)
S1+1 Steady Pulse Frequency
When S1+0 is set to 0 through 2, the value stored in the data register designated by operand S1+1 specifies the frequency
of the steady pulse output in percent of the maximum of the frequency range selected by S1+0. When S1+0 is set to 0 (10
to 1,000 Hz) or 1 (100 to 10,000 Hz), valid values for operand S1+1 are 1 through 100, thus the steady pulse frequency can
be 10 to 1,000 Hz or 100 to 10,000 Hz, respectively. When S1+0 is set to 2 (1,000 to 20,000 Hz), valid values for operand
S1+1 are 1 through 20 and the S1+1 value multiplied by 5 determines the steady pulse frequency, thus the steady pulse fre-
quency can be 1,000 to 20,000 Hz.
When S1+0 is set to 3, the value stored in the data register designated by operand S1+1 determines the frequency of the
steady pulse output directly. Valid values are 10 through 20,000.
S1+2 Initial Pulse Frequency
When S1+0 is set to 0 through 2, the value stored in the data register designated by operand S1+2 specifies the frequency
of the initial pulse output in percent of the maximum of the frequency range selected by S1+0. When S1+0 is set to 0 (10
to 1,000 Hz) or 1 (100 to 10,000 Hz), valid values for operand S1+2 are 1 through 100, thus the initial pulse frequency can
be 10 to 1,000 Hz or 100 to 10,000 Hz, respectively. When S1+0 is set to 2 (1,000 to 20,000 Hz), valid values for operand
S1+2 are 1 through 20 and the S1+2 value multiplied by 5 determines the initial pulse frequency, thus the initial pulse fre-
quency can be 1,000 to 20,000 Hz.
When S1+0 is set to 3, the value stored in the data register designated by operand S1+2 determines the frequency of the
initial pulse output directly. Valid values are 10 through 20,000.
S1+4
Reversible control enable
0: Reversible control disabled
1: Reversible control (single-pulse output)
2: Reversible control (dual-pulse output)
R/W
S1+5
Control direction
0: For ward
1: Reverse
R/W
S1+6
Preset value (high word)
1 to 100,000,000 (05F5 E100h)
R/W
S1+7
Preset value (low word)
S1+8
Current value (high word)
1 to 100,000,000 (05F5 E100h)
R
S1+9
Current value (low word)
S1+10
Error status
0 to 10
R
Operation Mode
Steady Pulse Frequency (Hz)
0 or 1
Maximum frequency (Hz) selected by S1+0
×
S1+1 value (%)
2
Maximum frequency (Hz) selected by S1+0
×
S1+1 value (
×
5%)
3
Steady pulse frequency (Hz) selected by S1+1
Operation Mode
Initial Pulse Frequency (Hz)
0 or 1
Maximum frequency (Hz) selected by S1+0
×
S1+2 value (%)
2
Maximum frequency (Hz) selected by S1+0
×
S1+2 value (
×
5%)
3
Initial pulse frequency (Hz) selected by S1+1
Operand
Function
Description
R/W
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...