« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
25-1
25: D
ATA
L
INK
C
OMMUNICATION
Introduction
This chapter describes the data link communication function used to set up a distributed control system.
A data link communication system consists of one master station and a maximum of 31 slave stations, each station com-
prising a 16- or 24-I/O type
MicroSmart
CPU module or any slim type CPU module. When the data link communication is
enabled, the master station has 12 data registers assigned for each slave station, and each slave station has 12 data registers
for communication with the master station. Using these data registers, the master station can send and receive data of 6
data registers to and from each slave station. No particular program is required for sending or receiving data in the data
link communication system.
When data of inputs, outputs, internal relays, timers, counters, or shift registers are moved to data registers using the move
instructions in the user program, these data can also be exchanged between the master and slave stations.
The
OpenNet Controller, MICRO
3
,
MICRO
3
C
, and FA-3S series PLCs can also be connected to the data link communica-
tion system.
The all-in-one 10-I/O type
MicroSmart
CPU module does not have data link communication capabilities.
Data Link Specifications
Electric Specifications
Compliance with EIA-RS485
Baud Rate
19,200 or 38,400 bps
Synchronization
Star t-stop synchronization
Star t bit:
1
Data bits:
7
Parity:
Even
Stop bit:
1
Communication Cable
Shielded twisted pair cable, core wire 0.3 mm
2
Maximum Cable Length
200m (656 feet) total
Maximum Slave Stations
31 slave stations
Refresh Mode
Separate refresh
Transmit/Receive Data
0 through 6 words each for transmission and receiving per slave station
Special Internal Relay
M8005-M8007:
communication control and error
M8080-M8116:
communication completion for each slave station
M8117:
communication completion for all slave stations
Data Register
D900-D1271:
transmit/receive data
Special Data Register
D8069-D8099:
communication error code
Master Station
Slave Station 1
Slave Station 31
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...