25: D
ATA
L
INK
C
OMMUNICATION
25-6
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
Special Internal Relays for Data Link Communication
Special internal relays M8005 through M8007 and M8080 through M8117 are assigned for the data link communication.
M8005 Data Link Communication Error
When an error occurs during communication in the data link system, M8005 turns on. The M8005 status is maintained
when the error is cleared and remains on until M8005 is reset using
WindLDR
or until the CPU is turned off. The cause of
the data link communication error can be checked using
Online
>
Monitor
, followed by
Online
>
PLC Status
>
Error
Status: Details
M8006 Data Link Communication Prohibit Flag (Master Station)
When M8006 at the master station is turned on in the data link system, data link communication is stopped. When M8006
is turned off, data link communication resumes. The M8006 status is maintained when the CPU is turned off and remains
on until M8006 is reset using
WindLDR
.
When M8006 is on at the master station, M8007 is turned on at slave stations in the data link system.
M8007 Data Link Communication Initialize Flag (Master Station)
Data Link Communication Stop Flag (Slave Station)
M8007 has a different function at the master or slave station of the data link communication system.
Master station: Data link communication initialize flag
When M8007 at the master station is turned on during operation, the link configuration is checked to initialize the data link
system. When a slave station is powered up after the master station, turn M8007 on to initialize the data link system. After
a data link system setup is changed, M8007 must also be turned on to ensure correct communication.
Slave station: Data link communication stop flag
When a slave station does not receive communication data from the master station for 10 seconds or more in the data link
system, M8007 turns on. When a slave station does not receive data in 10 seconds after initializing the data link system,
M8007 also turns on at the slave station. When the slave station receives correct communication data, M8007 turns off.
M8080-M8116 Slave Station Communication Completion Relay (Master Station)
Special internal relays M8080 through M8116 are used to indicate the completion of data refresh. When data link commu-
nication with a slave station is complete, a special internal relay assigned for the slave station is turned on for one scan
time at the master station.
M8080 Communication Completion Relay (Slave Station)
When data link communication with a master station is complete, special internal relay M8080 at the slave station is
turned on for one scan time.
M8117 All Slave Station Communication Completion Relay
When data link communication with all slave stations is complete, special internal relay M8117 at the master station is
turned on for one scan time. M8117 at slave stations does not go on.
Special Internal
Relay
Slave Station
Number
Special Internal
Relay
Slave Station
Number
Special Internal
Relay
Slave Station
Number
M8080
Slave Station 1
M8092
Slave Station 11
M8104
Slave Station 21
M8081
Slave Station 2
M8093
Slave Station 12
M8105
Slave Station 22
M8082
Slave Station 3
M8094
Slave Station 13
M8106
Slave Station 23
M8083
Slave Station 4
M8095
Slave Station 14
M8107
Slave Station 24
M8084
Slave Station 5
M8096
Slave Station 15
M8110
Slave Station 25
M8085
Slave Station 6
M8097
Slave Station 16
M8111
Slave Station 26
M8086
Slave Station 7
M8100
Slave Station 17
M8112
Slave Station 27
M8087
Slave Station 8
M8101
Slave Station 18
M8113
Slave Station 28
M8090
Slave Station 9
M8102
Slave Station 19
M8114
Slave Station 29
M8091
Slave Station 10
M8103
Slave Station 20
M8115
Slave Station 30
—
—
—
—
M8116
Slave Station 31
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...