25: D
ATA
L
INK
C
OMMUNICATION
25-4
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
Special Data Registers for Data Link Communication Error
In addition to data registers assigned for data communication, the master station has 31 special data registers and each
slave station has one special data register to store data link communication error codes. If any communication error occurs
in the data link system, communication error codes are set to a corresponding data register for link communication error at
the master station and to data register D8069 at the slave station. For details of link communication error codes, see below.
If a communication error occurs in the data link communication system, the data is resent two times. If the error still exists
after three attempts, then the error code is set to the data registers for data link communication error. Since the error code
is not communicated between the master and slave stations, error codes must be cleared individually.
Master Station
If any slave stations are not connected, master station data registers which are assigned to the vacant slave stations can be
used as ordinary data registers.
Slave Station
Note:
Slave station data registers D8070 through D8099 can be used as ordinar y data registers.
Data Link Communication Error Code
The data link error code is stored in the special data register allocated to indicate a communication error in the data link
system. When this error occurs, special internal relay M8005 (data link communication error) is also turned on at both
master and slave stations. The detailed information of general errors can be viewed using
WindLDR
. Select
Online
>
Mon-
itor
, then select
Online
>
PLC Status
>
Error Status: Details
When more than one error is detected in the data link system, the total of error codes is indicated. For example, when
framing error (error code 2h) and BCC error (error code 10h) are found, error code 12h (18) is stored.
Special Data
Register
Data Link Communication Error Data
Special Data
Register
Data Link Communication Error Data
D8069
Slave station 1 communication error
D8085
Slave station 17 communication error
D8070
Slave station 2 communication error
D8086
Slave station 18 communication error
D8071
Slave station 3 communication error
D8087
Slave station 19 communication error
D8072
Slave station 4 communication error
D8088
Slave station 20 communication error
D8073
Slave station 5 communication error
D8089
Slave station 21 communication error
D8074
Slave station 6 communication error
D8090
Slave station 22 communication error
D8075
Slave station 7 communication error
D8091
Slave station 23 communication error
D8076
Slave station 8 communication error
D8092
Slave station 24 communication error
D8077
Slave station 9 communication error
D8093
Slave station 25 communication error
D8078
Slave station 10 communication error
D8094
Slave station 26 communication error
D8079
Slave station 11 communication error
D8095
Slave station 27 communication error
D8080
Slave station 12 communication error
D8096
Slave station 28 communication error
D8081
Slave station 13 communication error
D8097
Slave station 29 communication error
D8082
Slave station 14 communication error
D8098
Slave station 30 communication error
D8083
Slave station 15 communication error
D8099
Slave station 31 communication error
D8084
Slave station 16 communication error
—
—
Special Data Register
Data Link Communication Error Data
D8069
Slave station communication error
Error Code
Error Details
1h (1)
Overrun error (data is received when the receive data registers are full)
2h (2)
Framing error (failure to detect star t or stop bit)
4h (4)
Parity error (an error was found by the parity check)
8h (8)
Receive timeout (line disconnection)
10h (16)
BCC (block check character) error (disparity with data received up to BCC)
20h (32)
Retr y cycle over (error occurred in all 3 trials of communication)
40h (64)
I/O definition quantity error (discrepancy of transmit/receive station number or data quantity)
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...