UEPO Jumper Cable Installation Procedure
1 UEPO cable
Note:
Remote EPO maybe required if IBF
(Internal Battery Feature) is installed. Refer
to your countries national electric code
requirements.
If this installation
DOES NOT
have a remote UEPO
(Unit Emergency Power Off) cable to be installed
skip this step.
1. At the front of the EPO panel in each frame
pull out gently on the locking actuator
switch and move the switch to active/up
position.
2. Connect the UEPO cable to J4 of the EPO
panel.
Note:
The UEPO cable is customer built
and supplied in accordance with the
specification in the IMPP
(GC22-7106).
3. If necessary, Repeat step
1
for each frame
installed.
Switch with
Locking Actuator
Connect Room
UEPO cable Here
Chapter 1. Beginning the Installation
1-9