191
Symptom
Cause/solution
Reference
No image is displayed on the HDMI
monitor.
• Does the HDMI output signal format match the
specifications of your monitor?
To fix the HDMI output signal format, set the signal
format supported by the monitor.
• Is an HDMI switcher used between this product and
the monitor? It may not work properly depending on
the specifications of the HDMI switcher. In addition,
please use an HDMI switcher that supports bus-
powered drive in a state where it operates with an
external power supply for stable operation.
• Is the cable in use compliant with the HDMI
specifications? It may not work with a cable not
compliant with the HDMI specifications. In addition,
please use an HDMI cable of 5m or less in length to
prevent deterioration of image quality and for stable
operation.
Installation
Guide
The thumbnail image of the camera
is displayed broken in the setup
menu of the web browser.
• Check that the JPEG data encryption is not set to "On"
in the camera setup menu.
−
Camera settings do not match the
monitoring system settings. The live
image on the monitor is not
displayed correctly. The camera
does not notify alarms.
• [Camera] - [The functions of this product will not
change the camera settings automatically] in
[Advanced setup] is not checked. When this setting is
checked, no camera settings are made. This may
cause each function of the monitoring system to fail to
operate properly.
PoE power supply stopped.
• If the PoE power supply to the camera exceeds the
power supply capacity of the IF1-WF01, the IF1-WF01
will stop PoE power supply. Reduce the number of
cameras connected to the PoE power supply, and then
click on the Error Resume button.
Note that the PoE total power supply warning occurs
when 80% of the power supply capacity is exceeded.
−