IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
3 Maintenance
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
28
Before conducting quarterly maintenance for the fire extinguishing system, notify the
related administrative departments that the fire extinguishing system will stop work during
the maintenance. In addition, disable the logical control function of the area or system to
prevent false alarms.
Before maintaining the system, ensure that all control cables to electromagnetic valve
drivers have been disconnected. This prevents the agent release due to misoperations, and
prevents accidental damage. After the maintenance is complete, reconnect the
electromagnetic valves and notify the administrative departments that the fire
extinguishing system has become operational.
Table 3-11
Quarterly maintenance checklist for the fire extinguishing system
Item
Method
Expected
Result
Troubleshooting
Fire control
panel
battery
1.
Disconnect the
AC power
when both the
DC and AC
power supplies
are normal, and
use batteries to
supply power to
the fire control
panel.
2.
Reconnect the
AC power
when the
battery voltage
drops to 23 V
DC.
The fire
control panel
reports a main
power supply
fault.
If the battery cannot be charged,
replace by following instructions in
the
Installing Fire Control Panel
Batteries
section in the solution
installation guide.
Fire alarm
bell
Simulate a scenario
to trigger the
smoke or heat
detector.
The alarm bell
rings loud and
clear.
1.
Check and reconnect cables to
the fire alarm bell.
2.
If the fault persists, replace by
following instructions in
Fire alarm
horn strobe
Simulate a scenario
to trigger the
smoke and heat
detectors at the
same time.
Flashes and
alarms are
generated loud
and clear.
1.
Check and reconnect cables to
the fire alarm horn strobe.
2.
If the fault persists, replace by
following instructions in
Replacing a Fire Alarm Horn
Strobe
3.3.5 Fire Extinguishing System (CE)