Item
Method
Expected Result
Troubleshooting
Emergency
lights
Remove the red
test button from
the emergency
lights.
The emergency
lights are on.
1.
Check and reconnect
power cables to the
emergency lights.
2.
If the fault persists,
replace by following
instructions in
Hand-held
fire
extinguisher
Check the
hand-held fire
extinguisher.
The fire extinguisher
is intact.
If the fire extinguisher is
damaged, replace it.
The fire extinguisher
is within the validity
period.
If the fire extinguisher has
expired, replace it.
3.2.6 Other Systems
Table 3-7
Monthly maintenance checklist for other systems
Item
Method
Expected Result
Troubleshooting
Containers
Check the
container exterior
for damage or
corrosion.
The container and
bases are free from
paint flake-off, rust, or
corrosion.
Maintain or replace the
rusty or damaged part of the
containers. For details, see
the
Paint Repair
section in
the installation guide.
External
cable trays
Check whether the
cables and cable
trays are intact.
Cables and cable trays
are intact without
serious aging.
Replace seriously aged
cables. For details, see the
installation guide.
External
environmen
t of
containers
Check whether
hazards or
potential hazards
exist around the
containers.
No hazard or potential
hazard exist around the
containers.
Take measures to handle
potential hazards.
Check whether
obvious rubbish
exists around the
containers.
No obvious rubbish
exists around the
containers.
Clean the rubbish.
Check whether the
ambient
temperature,
humidity, and solar
radiation outside
the containers meet
requirements.
The ambient
temperature, humidity,
and solar radiation are
consistent with the
specific project
requirements.
For details, contact Huawei
technical support.