IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
3 Maintenance
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
42
Categ
ory
Item
Method
Expected
Result
Troubleshooting
Circuit
breakers
Manual switch
off and on the
circuit breakers
five times.
The circuit
breakers
operate
smoothly.
If a circuit breaker does not
operate smoothly, repair or
replace the circuit breaker. For
details about how to replace a
circuit breaker, see the
replacement instructions for
the circuit breaker.
Fastening
bolts
between
power
cables
and the
busbar
After the
equipment is
powered off,
perform the
following
steps:
Observe
whether the
cables
deteriorate
seriously.
Observe
whether the
cable
insulation
layers are in
good
condition.
Measure the
insulation
resistance of
cables.
Check
whether the
labels on
cables are
intact and
clear.
Check
whether the
fastening
bolts are
tightened.
The cables
do not
deteriorate
and
insulation
layers are in
good
condition.
The cable
insulation
resistance is
not less than
5 megohm.
The labels
are clear
and intact.
The
fastening
bolts are
tightened.
Replace a cable if it has
deteriorated seriously and
its insulation has failed. For
more specific information,
contact Huawei technical
support.
Tighten a bolt if it is loose.
Replace a label if it is
damaged or blurry. For
details connect Huawei
technical support.
NOTE
You are advised to perform this
operation only when the
All-in-one or power distribution
equipment is powered off for
maintenance.
UPS5000
-E
Power cables
and terminals
(between the
UPS and the
PDC).
Cables and
terminals are
free from
deterioration,
damage, spark
signs, and loose
contacts.
Replace cables or secure output