IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
5 Parts Replacement
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
116
Step 2
Remove the terminals connected to the electronic lock.
Step 3
Remove the screws under the electronic lock using a Phillips screwdriver, and remove the
faulty electronic lock, as shown in
Figure 5-33
Removing the electronic lock
Step 4
Install a new electronic lock and connect the terminals.
Step 5
Reinstall the baffle plate.
Step 6
Check that the new electronic lock is working properly.
If the electronic lock indicator is green when the container door is closed and red when the door is open,
the electronic lock is working properly.
----End
Follow-up Procedure
Dispose of the removed electronic lock that is confirmed faulty.
5.3.13.5 Replacing an Emergency Door Release Button
Prerequisites
The emergency door release button needs to be replaced.
A spare emergency door release button of the same model is available and functional.
Impact on the System
None
Preparations
Tools: insulation tape, step ladder (2 m), Phillips screwdriver, protective gloves
Material: spare emergency door release button
Documents required: none