If a container is on fire, do not enter the container or stay around the container before the
fire is extinguished.
After pressing the start switch (green one) of the emergency start/abort switch, leave the
site immediately and wait for the firefighters to handle the situation.
Step 5
Check whether there is an alarm on the fire control panel outside the container.
Step 6
If the fire control panel reports no composite fire alarm, check the cable connection from the
fire control panel to the management system.
If the cable connection is correct and the alarm disappears, the troubleshooting ends.
If the cable connection is correct but the alarm persists, go to
Step 7
Check the threshold settings for the fire control panel in the management system.
If the settings are correct and the alarm disappears, the troubleshooting ends.
If the settings are correct but the alarm persists, contact Huawei technical support.
----End
Follow-up Procedure
Analyze the cause of the fault, and work out and record the preventive measures.
6.13 Emergency Operations for a Gas Release Alarm (CE)
Prerequisites
The management system reports a composite fire alarm.
The following composite fire alarm emergency operations are for reference only.
If a fire alarm is generated, determine whether to extinguish the fire or leave the area
immediately based on the actual situation and contact the personnel on duty or local fire
station.
Procedure
Step 1
Locate the fire alarm area based on the alarm information.
Step 2
Check the internal situation in the video surveillance system.
If the video surveillance system indicates that everything is normal, go to