IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
5 Parts Replacement
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
132
Step 4
Remove the faulty VESDA battery using a Phillips screwdriver, and install the spare VESDA
battery into the power box.
Step 5
Connect battery cables.
Distinguish between the positive and negative battery terminals when connecting battery
cables.
----End
Follow-up Procedure
Dispose of the removed VESDA power box battery that is confirmed faulty.
5.4.8 Replacing a Fire Cylinder
Prerequisites
A fire cylinder needs to be replaced.
A spare fire cylinder of the same model is available and functional.
Impact on the System
None
Preparations
Tools: pallet truck, Phillips screwdriver, adjustable wrench, protective gloves
Materials: spare fire cylinder
Documents required: fire extinguishing device layout diagram
Skill requirement: fire extinguishing engineer
For the diagram, see the initial configuration guide.
Procedure
Step 1
Move the fire cylinder to the place where a faulty fire cylinder needs to be replaced.