5 Parts Replacement
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
81
Check that the standby power supply to the rPDU is available.
Impact on the System
None
Preparations
Tools: protective gloves, Phillips screwdriver, step ladder
Material: spare rPDU
Documents required: none
Skill requirement: electrician's work permit
Procedure
Step 1
Switch off the circuit breaker of the faulty rPDU in the PDC.
Step 2
Remove the baffle plate from the top of the cabinet using a Phillips screwdriver.
Step 3
Remove all power connectors from the rPDU.
Step 4
Remove the rPDU power cable on the top of the cabinet.
Step 5
Loosen the screws from the support of the rPDU at the upper and lower sides of the front
panel using a Phillips screwdriver until the rPDU can be taken out, as shown in
Figure 5-5
Removing screws a the upper and lower sides of the rPDU
Step 6
Lift the faulty rPDU and take it out.
Step 7
Remove the support and screws from the faulty rPDU and install them on a new rPDU.
Step 8
Mount the new rPDU with a support into the cabinet, and tighten the fastening screws of the
rPDU using a Phillips screwdriver, as shown in