IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
3 Maintenance
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
40
Item
Method
Expected Result
Troubleshooting
sampling pipe.
The VESDA sends
an alarm signal to the
host.
See documents delivered with
the VESDA.
Check the VESDA
operation panel.
All indicators are
normal.
See documents delivered with
the VESDA.
Check whether the
backup power is
working properly,
and whether the
VESDA restarts
normally after the
mains and host are
powered off.
The backup power is
working properly,
and the VESDA
restarts normally
after the mains and
host are powered off.
See documents delivered with
the VESDA.
VESDA
power
supply
Check the power
indicator.
The Power indicator
is on.
1.
Check the power cables.
2.
Replace by following
instructions in
Replacing a Battery in the
VESDA Power Box
3.4.6 Other Systems
Table 3-19
Semi-annual maintenance checklist for other systems
Item
Method
Expected Result
Troubleshooting
Lights
Check whether
the lights can be
switched on
normally.
The lights turn on
normally.
1.
If a light cannot be
switched on, check
whether the light is
securely installed and in
good contact with the
light base.
2.
If a light is securely
installed and in good
contact with the light base
but fails to turn on,
replace the light.
Ventilati
on vent
air filter
Check whether
the filter is
blocked.
The air filter is not
blocked.
If an air filter is slightly
blocked, clean the air filter
and reinstall it. If more than
50% of the meshes are
blocked, replace the air filter
by following instructions in
5.2.5 Replacing a Ventilation
Vent Air Filter
Cable
trays
inside
Check whether
the cable trays
are securely
Cable trays are properly
installed, and fasteners are
secure.
Secure cable trays that have
become loose.