IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
5 Parts Replacement
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
93
5.3 Replacing Monitoring System Components
5.3.1 Replacing a T/H Sensor
Prerequisites
A T/H sensor needs to be replaced.
A spare T/H sensor of the same model is available and functional.
Impact on the System
None
Preparations
Tools: flat-head screwdriver (5–10 mm), insulation tape, step ladder (2 m), protective gloves
Material: spare T/H sensor
Documents required: monitoring device layout diagram, initial configuration parameters for
the management system
Skill requirement: weak-current engineer
For the diagram and table, see the initial configuration guide.
Procedure
Step 1
Press the clamp strip and remove the cover of the T/H sensor, as shown in
Figure 5-12
Removing the T/H sensor
Step 2
Remove the network cable from the T/H sensor. Install a new T/H sensor and reconnect the
network cable to the sensor.
Step 3
Reset parameters by referring to the management system initial configuration guide.