6 Emergency Operations
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
157
The access controller is faulty. Replace it by following instructions in
Step 4
(Optional) After the fault is rectified, replace by following instructions in
an Emergency Door Release Button
----End
Follow-up Procedure
Analyze the cause of the fault, and work out and record the preventive measures.
6.9 Emergency Operations for Container Door Open
Prerequisites
A door open alarm is generated for the IDS1000.
Procedure
Step 1
Locate the door based on the alarm information.
Step 2
Enter the container, verify that no device is lost and the system is working properly. Then
close the container door.
Step 3
Check whether the alarm is cleared.
If yes, no further action is required.
If no, go to
----End
Follow-up Procedure
Analyze the cause of the fault, and work out and record the preventive measures.
6.10 Emergency Operations for an Early Fire Alarm
Prerequisites
The VESDA has generated a fire alarm.
The following early fire alarm emergency operations are for reference only.