Pay attention to the negative and positive polarities of the power supply. If the polarities are
connected incorrectly, the device may be burned.
Step 6
Configure the new hydrogen collector based on the DIP switch settings for the removed
hydrogen collector.
Step 7
Switch on the circuit breaker of the hydrogen collector, and check whether it is working
properly.
If the hydrogen density displayed on the hydrogen collector, the hydrogen collector is working properly.
----End
Follow-up Procedure
Dispose of the removed hydrogen collector that is confirmed faulty.
5.3.7 Replacing a Hydrogen Exhaust Fan
Prerequisites
A hydrogen exhaust fan needs to be replaced.
A spare hydrogen exhaust fan of the same model is available and functional.
Impact on the System
None
Preparations
Tools: Phillips screwdriver, cable cutter, insulation tape, step ladder, protective gloves
Material: quick-connect terminals, spare hydrogen exhaust fan
Document: power supply and distribution system diagram
Skill requirement: weak-current engineer
For the diagram, see the initial configuration guide.
Procedure
Step 1
Switch off the power circuit breaker of the hydrogen collector.
Step 2
Open the cable trough, and cut off the power cable to the hydrogen exhaust fan using a cable
cutter.
Reserve a segment of the power cable at the quick-connect terminal when cutting the power cable to the
hydrogen exhaust fan.