IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
3 Maintenance
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
15
Item
Method
Expected
Result
Troubleshooting
Check electric
heaters.
The electric
heaters and
switches are
secure.
Secure the electric heaters and
switches.
The electric
heater surface
is not
corroded.
Replace the electric heater by
following instructions in the air
conditioner user manual.
Check the
temperature-humid
ity sensor.
Check that T/H
sensors in the
air conditioner
and aisles are
securely
installed.
Secure the T/H sensor.
Check the water
sensor.
The water
sensor is
secure, and the
two downward
metal
conductive
plates do not
touch with
each other and
are free from
corrosion.
Replace the water sensor by
following instructions in the air
conditioner user manual.
Thermal
insulation
foam for
the
humidifier/
condensate
drainpipe
Check whether the
thermal insulation
layers are in good
condition without
condensation.
The thermal
insulation
layers are in
good condition
and free from
condensation.
If there is condensation under a
pipe, replace the thermal insulation
layer by following instructions in
5.2.6 Replacing a Thermal
Insulation Layer
If a cooling component needs to be powered off for maintenance, take measures to prevent
device overheating before powering off the component.