FusionModule1000A40 ICT Solution
Maintenance Guide
4 Parts Replacement
Issue 01 (2019-03-05)
Copyright © Huawei Technologies Co., Ltd.
141
Figure 4-85
Connecting cables to the electromagnetic valve
Step 9
Connect the cables to the pressure announciator.
Step 10
Reinstall the adapter and high-pressure hose.
Step 11
Connect the cables between the electromagnetic valve and the fire alarm control panel.
Step 12
After installing the fire cylinder, remove the safety pin on the fire cylinder.
Verify that the safety pin is removed after the system starts working properly; otherwise, the
electromagnetic valve may fail to start, and extinguishant may fail to be released in the case of
a fire.
1.
Remove screws securing a safety pin.