FusionModule1000A40 ICT Solution
Maintenance Guide
3 Routine Maintenance
Issue 01 (2019-03-05)
Copyright © Huawei Technologies Co., Ltd.
43
Device
Operation
Check Standard
Maintenance Guide
Heat
detector
Heat the heat
detector using a
heating device.
1.
If the temperature
is below the alarm
threshold, the
alarm indicator
blinks once every
6s.
2.
If the temperature
is above the alarm
threshold, the
indicator turns on.
The extinguishant
control panel
generates an
alarm and triggers
the fire alarm bell.
Replace by following
instructions in 4.4.2.2
Replacing a Heat Detector
(CE).
Smoke
detector
Release smoke
onto the smoke
detector using a
smoke pistol.
1.
If the smoke
density is below
the alarm
threshold, the
alarm indicator
blinks once every
6s.
2.
If the smoke
density is above
the alarm
threshold, the
indicator turns on.
The extinguishant
control panel
generates an
alarm and triggers
the fire alarm bell.
Replace by following
instructions in 4.4.2.1
Replacing a Smoke Detector
(CE).
Extinguisha
nt abort
button
1.
After the
manual gas
release button is
pressed on the
extinguishant
control panel,
the gas release
countdown
starts. Then,
press the
extinguishant
abort button.
2.
Reset the
extinguishant
abort button by
rotating it
counterclockwi
se.
1.
After the
extinguishant
abort button is
pressed, the gas
release
countdown stops.
2.
After the
extinguishant
abort button is
reset, the gas
release
countdown starts
from zero again.
Replace by following
instructions in 4.4.2.7
Replacing the Extinguishant
Abort Button (CE).