Device
Operation
Check Standard
Maintenance Guide
Horn strobe
Press the manual
gas release button
on the
extinguishant
control panel.
The horn strobe
generates glaring
flashes and shrill
alarms.
For details, see 4.4.2.4
Replacing an Internal Horn
Strobe (CE) or 4.4.2.5
Replacing an External Horn
Strobe (CE).
VESDA
Check the VESDA
sampling pipes.
The supports and
connectors of the
sampling pipes are
securely connected.
Replace damaged sampling
pipes, and apply glue where
pipes are not well sealed.
Remove or block a
sampling pipe.
An alarm is
generated.
See documents delivered with
the VESDA.
Release smoke to
the furthest end of
a VESDA
sampling pipe.
The VESDA
generates an alarm in
120s.
See documents delivered with
the VESDA.
The VESDA panel
displays an alarm.
See documents delivered with
the VESDA.
Check the VESDA
operation panel.
All indicators are
normal.
See documents delivered with
the VESDA.
Check whether the
backup power is
working properly,
and whether the
VESDA restarts
normally after the
mains powered is
disconnected.
The backup power is
working properly,
and the VESDA
restarts normally
after the mains power
is disconnected.
See documents delivered with
the VESDA.
VESDA
power
supply
Check the power
indicator.
The power indicator
turns on.
1.
Check the power cables.
2.
Replace by following
instructions in 4.4.3
Replacing Batteries for the
VESDA Power Box.
3.7.6 Other Systems
Table 3-19
Semi-annual maintenance checklist for other systems
Item
Method
Check
Standard
Troubleshooting