FusionModule1000A40 ICT Solution
Maintenance Guide
3 Routine Maintenance
Issue 01 (2019-03-05)
Copyright © Huawei Technologies Co., Ltd.
26
Item
Method
Check
Standard
Troubleshooting
Check whether
obvious rubbish
exists around the
containers.
No obvious
rubbish exists
around the
containers.
Clean the rubbish.
Check whether the
ambient
temperature,
humidity, and solar
radiation outside
the containers meet
requirements.
The external
temperature
and solar
radiation
requirements
of the
FusionModule
1000 are as
follows:
Temperatur
e:
−
Normal
tempera
ture:
-20°C to
+55°C
−
Low
tempera
ture:
-40°C to
+45°C
Humidity:
5%–95%
RH
Solar
radiation: ≤
1120 W/m
2
For details, contact Huawei
technical support.
3.6 Quarterly Maintenance
3.6.1 Monitoring System
Table 3-10
Quarterly maintenance checklist for the monitoring system
Check
Item
Operation
Check Standard
Troubleshooting
Access
actuator
Power input
Input voltage:
36–60 V DC
Check the input power cables if the
input voltage is abnormal.