Step 6
Remove the screws using a Phillips screwdriver, and take out the faulty fire alarm control
panel.
Step 7
Install the new fire alarm control panel in the same position.
Step 8
Put the corrugated pipes and cables back to the box, and reconnect the cables according to
labels.
Step 9
Install the battery in the same position, and connect cables in the same way.
Figure 4-91
Connecting battery cables
Step 10
Use a Phillips screwdriver to secure the battery fixing plate.
Figure 4-92
Installing the battery fixing plate
Step 11
Switch on the circuit breaker for the fire extinguishing PDB.
Step 12
Switch on the active and standby power supplies to the fire alarm control panel.
Step 13
Check whether the new fire alarm control panel is working properly.
If the power indicator is on and the alarm indicator is off, the fire alarm control panel is working
properly.