FusionModule1000A40 ICT Solution
Maintenance Guide
3 Routine Maintenance
Issue 01 (2019-03-05)
Copyright © Huawei Technologies Co., Ltd.
35
Item
Method
Check Standard
Troubleshooting
Monitori
ng
Export air
conditioner
logs, alarms,
temperature,
humidity, the
operating
status of the
compressor,
fan, electric
heater, electric
humidifier, and
water pump,
and time from
the monitoring
system. View
the historical
alarms
generated in
this quarter and
select the most
common five
ones (skip this
step if no
monitoring
system is
configured).
N/A
Rectify the fault or contact
Huawei technical support.
Electric
heater
The electric
heater is
secure.
The electric heater is
securely installed.
Secure the electric heater and
switch.
Check that the
electric heater
surfaces are
not eroded.
The electric heater surface is
not corroded.
Replace the electric heater if
its surface is eroded.
Compon
ents
inside
the
electric
control
box
(Remove
the
electric
Check that all
circuit breakers
and fuses work
properly.
Switches and fuses are
working properly.
Replace faulty circuit
breakers and fuses.
Check that the
cable
connection is
secure and
correct.
Cables are securely
connected.
Secure loose cables.