3 Routine Maintenance
Issue 01 (2019-03-05)
Copyright © Huawei Technologies Co., Ltd.
42
Semi-annual maintenance of the fire extinguishing system involves system commissioning.
Before the maintenance, inform the related administrative departments that the fire
extinguishing system will be maintained and stop working.
Before maintaining the fire extinguishing system, remove the electrical actuator from the
container valve of the fire cylinder. This prevents the extinguishant release due to
misoperations, and prevents accidental damage.
After the maintenance, reconnect the electrical actuator, and inform the administrative
departments that the fire extinguishing system has become operational.
Table 3-18
Semi-annual maintenance checklist for the fire extinguishing system
Device
Operation
Check Standard
Maintenance Guide
Fire
extinguishi
ng system
commission
ing
Commission the
fire extinguishing
system by
following the
instructions in the
Fire
Extinguishing
System
Commissioning
(CE)
section in the
commissioning
guide for the
solution in use.
Devices work
properly, and the
management system
displays related
alarms.
Replace by following
instructions in 4.4.2
Replacing Fire Extinguishing
System Devices (CE).
Fire alarm
bell
Flip the key to
Enable Control
on
the extinguishant
control panel
rightward. Press
Silence/Sound
Alarm
to start or
abort the fire alarm
bell. Reset the key
to
Enable Control
by flipping it
leftward.
The alarm bell rings
normally. The alarm
bell rings loud and
clear when it is
started.
1.
Check and reconnect
cables to the fire alarm
bell.
2.
If the fault persists,
replace by following
instructions in 4.4.2.6
Replacing a Fire Alarm
Bell (CE).
Warning
sign
Pull up the reset
button on the
pneumatic switch.
The warning sign
indicator is on.
Replace by following
instructions in 4.4.2.3
Replacing Warning Signs
(CE).