FusionModule1000A40 ICT Solution
Maintenance Guide
4 Parts Replacement
Issue 01 (2019-03-05)
Copyright © Huawei Technologies Co., Ltd.
130
Figure 4-71
Installing the cover
Step 8
Switch on the active and standby power supplies to the fire alarm control panel, and check
whether the new horn strobe is working properly.
Unlock the fire alarm control panel and press
HORN/STROBE
. The horn strobe should be activated.
----End
Follow-up Procedure
Dispose of the removed horn strobe that is confirmed faulty.
4.4.1.6 Replacing a Fire Alarm Sounder (Standard)
Prerequisites
A spare fire alarm sounder of the same model is available and functional.
Impact on the System
The fire extinguishing system stops working during the replacement.
Preparations
Tools: needle-nose pliers, insulation tape, protective gloves, step ladder
Materials: spare fire alarm sounder, cord end terminals
Documents: fire extinguishing device layout diagram (standard)
Skill requirement: fire engineer